Heat Exchanger Types and Selection
In order to achieve optimum process operations,
it is essential to use the right type of process equipment in any given process. Heat exchangers, commonly used to transfer
energy from one fluid to another, are no exception.
The selection of the proper type of heat exchangers is of critical importance.
Selecting the wrong type can lead to sub-optimum plant performance, operability issues and equipment failure.
The following
criteria can help in selecting the type of heat exchanger best suited for a given process: - Application (i.e. sensible vapor or liquid, condensing or boiling)
- Operating pressures & temperatures (including startup, shutdown, normal & process upset conditions)
- Fouling characteristics of the fluids (i.e. tendency to foul due to temperature,
suspended solids ...)
- Available utilities (cooling
tower water, once through cooling water, chilled water, steam, hot oil...)
- Temperature driving force (i.e. temperature of approach or cross and available LMTD)
- Plot plan & layout constraints
- Accessibility
for cleaning and maintenance
- Considerations for future
expansions
- Mechanical considerations such as: 1) material
of construction; 2) thermal stresses (during startup, shutdown; process upset and clean out conditions); 3) impingement protection
Shell-and-tube heat exchangers accounts for more than 50% of all heat exchangers
installed. However, in many cases, there are more attractive alternatives in terms of cost and energy recovery.
Any time a heat exchanger is being replaced, the opportunity should be taken to re-assess if the type used is best for the
given process. Operating changes since initial installation as well as advancements in the field of heat transfer may
point towards a different type as being optimal.
Heat Exchangers Types
Shell & tube heat exchangers Baffle types
Segmental
baffles
Double
segmental baffles
No-tube-in-window
(NTIW) baffles
Rod
baffles
EM
baffles
Helical
baffles
Tube Enhancements
Twisted
tubes
Low
finned tubes
Tubes
inserts (twisted tapes, Cal Gavin)
Compact type heat exchangers
Plate & frame heat exchangers (gasketed, semi-welded, welded)
Spiral
Blazed plate & frame
Plate-fin heat exchanger
Printed circuits
Air-cooled heat exchangers
Heat Exchangers Selection
Past experience, is always the best place to start to guide the selection of heat exchanger types.
Understanding the reasons behind both successes and failures will lead to better equipment selection.
When comparing different types of heat transfer equipment, one must take into
consideration the total cost of the equipment which includes:
- purchase cost
- installation cost
- operating cost (pumping, fan…)
- maintenance
cost
In order to make the best selection, it is important
to have some knowledge of the different types of heat exchangers and how they operate. The
tables below offer the advantages and disadvantages of common types of heat exchangers. They can be used
to arrive at a type that is best suited for a given process.
Shell & tube heat exchangers |
Advantages | Disadvantages |
Widely known and understood since it is the most common type | Less thermally
efficient than other types of heat transfer equipment |
Most versatile in terms of types of service | Subject to flow induced vibration which Can lead to equipment failure |
Widest range of allowable design pressures and temperatures | Not well suited for temperature cross conditions (multiple units in series must
be used) |
Rugged mechanical construction - can withstand more abuse (physical and process)
| Contains stagnant zones (dead zones) on the shell side which
can lead to corrosion problems |
| Subject to flow mal-distribution especially with two phase
inlet streams |
Compact Heat
Exchangers |
Advantages | Disadvantages |
Low initial purchase cost (plate type) | Narrower rage of allowable
pressures and temperatures |
Many different configurations are available (gasketed, semi-welded, welded,
spiral) | Subject to plugging/fouling due to very narrow flow path |
High heat transfer coefficients (3 or more times greater than for shell & tube heat exchangers, due to much higher
wall shear stress) | Gasketed units require specialized opening and closing procedures |
Tend to exhibit lower
fouling characteristics due to the high turbulence within the exchanger | Material of construction selection is critical since
wall thickness very thin (typically less than 10 mm) |
True countercurrent designs allow significant temperature crosses to be achieved
| |
Require small footprint
for installation and have small volume hold-up | |
Air Cooled
Heat Exchangers |
Advantages | Disadvantages |
Attractive option for locations where cooling water is scarce
or expensive to treat | High initial purchase cost |
Well suited for cooling high temperature process streams (above 80oC when using cooling water should be
avoided) | Require relatively large footprint |
Low maintenance and operating costs (typically 30-50% less than cooling water) | Higher process outlet temperature (10-20 oF above the ambient dry bulb temperature) |